MALONEY SPECIAL ELASTOMERS FULL FACE FLANGE GASKET
Full Faced Style Gasket
Available in the following compounds:
COMPOUNDS: MAX SERVICE TEMPERATURE: COMMON USES:
Water & Sewer Air
EPDM 212°F 150°F Vegetable Oil, Alcohols, Dilute Acids,
Diluted Alkalis, MEK, Acetone, fresh
water, sea water, storm water,
sanitary sewage & reclaimed water
Nitrile 150°F 125°F Fresh water, salt water, sanitary
sewage, storm water, petroleum
products, oils, fats, chemicals, greases
Neoprene 200°F 150°F Fresh water, salt water, sanitary
sewage, storm water, greases
FKM 212°F 300°F Fresh water, salt water, storm
water, aromatic hydrocarbons, fuels,
Acids, vegetable oils, petroleum
Products, and most chemicals and
Solvent
● Sizes 4” – 36”, 1/8” Nominal Thickness ● Holes match ANSI A-21.10, A21.15 and B 16.1 Class 125
Flange drilling.
● Rated for a water working pressure of 350psi ● Designed for unique surface of Ductile Iron Flange joints
For 4”-24” and 250psi for 30”-36” and are based
on maximum rating of C110, C111 & C153 ● Employs three ring type pieces mold into the gasket that
flange project beyond both sides of the main surface of the
Gasket to greatly improve sealing and reduces bolt
torque required to seal the joint
TECHNICAL DATA MALONEY SPECIAL ELASTOMERS FULL FACE FLANGE GASKET
Size BC Pressure Number Working Pressure/Bolt Torque
Inches Inches Rating Bolt Holes 250 psi 350psi
4 7.50 350psi 8 90 110
6 9.50 350psi 8 90 110
8 11.75 350psi 8 90 110
10 14.25 350psi 12 90 130
12 17.00 350psi 12 90 130
14 18.75 350psi 12 110 150
16 21.25 350psi 16 110 160
18 22.75 350psi 16 120 180
20 25.00 350psi 20 120 200
24 29.50 350psi 20 130 220
30 36.00 250psi 28 140 –
36 42.75 250psi 32 160 –
Bolt holes match ANSI A21.10, A21.15 AND B16.1. All gaskets meet the requirements shown in the appendices of AWWA C110, C111 and C115.
Prior to assembly, make sure the flanges are free of sand, grit, grease or other foreign material.
Hand tighten all bolts and check for alignment. Use a crisscross pattern to tighten the bolts, starting with the top bolt then the bottom bolt 180° from the top bolt, then 90° to the left and tighten that bolt, then 180° to the right across form it then one bolt to the right and repeat the crisscrossing for the remainder of the bolts. Flange bolts must be evenly torqued in stages to provide proper sealing.
Call Maloney Technical Product Customer Service Representative with the project specifications for recommendation on best compound to use for a special application, current lead times and for pricing. Maloney maintains inventory on many of the sizes and special compounds.
BROCHURE, Special Compound Full Face Flg. Gasket